red line

CONTROL PANELS, DETECTORS AND PUSH-BUTTON

40-1

The automatic smoke detection system consist in the electronic control panel and the accessories. The built-in floating batteries guarantee the system operation also in case of main supply failure.

SINGLE ZONE ELECTRONIC CONTROL PANEL

(part n° 36414K)
The small size electronic control panel is provided with lock and floating battery, and allows to connect: In case of alarm, the control panel sends a 24 Vdc signal to maximum n°l 0 pyrotechnic devices, which are installed in the thermal valves and/or in the thermal valves with selectors.
VOLTAGE SUPPLY 230 Vac
OUTPUT 24dc/l,5A
SIREN OUTPUT 24Vdc/0,5mA
AUTONOMY 2 hours with standard floating battery
DETECTORS smoke/temperature (n. 10) x 2 lines - max 20)

EMERGENCY PUSH-BUTTON

(part n° 37170K)
To operate the emergency push-button it's necessary to break the nonshattering prelanced glass.
It's provided with a test device.
The box is red.
IP 40 protection class, manufactured according to the BS5839 regulations part II (CEN-EN 54 part IV).

OPTICAL SMOKE DETECTOR

(part n° 36418Q)
Smoke detection by infrared light diffusion for Tyndall effect. It's certified according to the UNI EN 54 - 7/9 regulations.
Alarm signal through the red LED (light emitting diode).
RESPONSE TIME 3 s approx.
VOLTAGE SUPPLY 10 - 30 Vdc
TEMPERATURE RANGE -10° / 80° C
DEGREE OF HUMIDITY < 95%
DETECTED SURFACE 40 mq
A frequent cleaning, especially in dusty ambients, is recommended.